SPECIFICATIONS
Light Source GaAlAs Infrared LED
Operating Voltage Nominal: 12 VDC or 24 VDC
Working Voltage 8.0 - 35.0 VDC
(35.0 VDC Max)
Wave Form Filtered DC 15% Ripple Max.
Alarm Current 150mA Maximum
Surge Current 200μA Maximum (2 wire)
Average Stand-By 38μA AVG @12 VDC
Current 55μA AVG @24 VDC
70μA AVG @35 VDC
Ambient Temperature 32° F - 120° F (0° C - 49° C)
Sensitivity Test Feature Automatic Sensitivity
Window Verification Test
Compatibility Identifier HD-6
Order Codes
2-Wire Detector & Trim Ring
Bone SLR-835B-2
White SLR-835B-2W
4-Wire Detector & Trim Ring
Bone SLR-835B-4
White SLR-835B-4W
STANDARD FEATURES
• Low Profile - Only 2.0" High
• 2 or 4 Wire Models
• Highly Stable Operation, RF/Transient Protection
• Two built-in power/sensitivity supervision/alarm LED's
• Non-Directional Smoke Chamber
• Vandal Resistant Security Locking Feature
• Removable smoke labyrinth for cleaning or
replacement
• Automatic Sensitivity window verification function
meets outlined requirements in NFPA 72,
Inspection,Testing and Maintenance
APPLICATION
The HOCHIKI America SLR-835B Series can be used in
all areas where Photoelectric Smoke Detectors are required.
It is suited for smoldering or flaming fires.
OPERATION
The SLR-835B Series photoelectric smoke detector
utilizes two bicolored LED's for indication of status. In
a normal standby condition the LED's flash Green every
3 seconds. When the detector senses that its sensitivity
has drifted outside the UL listed sensitivity window the
LED's will flash Red every 3 seconds. When the detector
senses smoke and goes into alarm the status LED's
will latch on Red.
The unit is comprised of an LED light source and silicon
photo diode receiving element. In a normal standby
condition, the receiving element receives no light from
pulsing light source. In the event of fire, smoke enters
the detector and light is reflected from the smoke
particles to the receiving element. The light received is
converted to an electronic signal. Signals are processed
in the comparator, and when two consecutive signals
exceeding the basic level are received within a specific
period of time, the time delay circuit triggers the SCR
switch to activate the alarm signal. The status LED
lights continuously during alarm period.