Product Code:
Agency Listings • UL Listed Control Units and Accessories for Fire Alarm Systems (UL864) Standard for Safety for Fire Protective Signaling Systems (UL1481) File# S5075. • CSFM - California State Fire Marshal Approved. File # 7315-1335:103. • MEA - NYC Department of Buildings Approved. Features/Specifications Power Supply/Charger: • 12VDC or 24VDC selectable output. • 6.5 amp max total alarm current. • 115VAC 60Hz., 3.2 amp. • Short circuit and thermal overload protection. • Built-in charger for sealed lead acid or gel type battery backup. • Maximum charge current .7 amp. • Zero voltage drop upon transfer to battery backup. • AC input and DC output LED indicators. • AC fail supervision (form "C" contact rated @ 1 amp 28VDC). • Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC). • Lifetime Warranty. Logic Board: • Class 2 Rated power limited outputs. • Two (2) Class A or two (2) Class B FACP inputs. • Two (2) Class A or four (4) Class B Indicating Circuits. • Two (2) Class B outputs may be paralleled for more power on an indicating circuit. • One (1) Aux. Power Output @ 1 amp supply current (w/Battery Back Up). • Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occured on one or more signaling circuit outputs. • Input to Output Follower Mode (maintains synchronization of notification appliance circuits). • Compatible with 24VDC or 12VDC fire panels. • Common Trouble inputs and outputs. • Ground fault detection. • Lifetime Warranty. Enclosure • Accommodates up to two (2) 12VDC/12AH batteries. • Dimensions: 15.5”H x 12”W x 4.5”D • 1/2 and 3/4 combination knockouts.