Edwards Signals ED-FSC1004R Fire Shield Plus 10Zone Red 120v The Edwards FireShield fire alarm family consists of 1*, 3, 5 and 10 zone conventional fire alarm control panels, and integrated DACT/Dialer*, serial annunciator modules, and serial remote relay modules. All of these components are microprocessor-controlled. The FireShield family is ideal for both new and retrofit installations alike.Edwards FireShield incorporates features designed to simplify installation, operation and maintenance. These include front panel programming, one person walk testing, and selectable IDC and NAC types. In addition, these panels have combination waterflow and supervision IDC.Options for the FireShield panels include serial bus relay modules programmable for common or zone activation, serial bus remote annunciators, city tie and reverse polarity modules, and optional trim rings for semi-flush mounting. An optional fully integrated DACT/Dialer provides 32 character LCD display, event history log, support for Contact ID and SIA DCS 4/2, and upload/download of Panel/DACT configuration, status and event history.FireShield panels are powerful enough to meet the demands of today's installations while leaving plenty of room to grow in the future. All available current may be used for notification appliances, or up to 0.5 mps can be used as auxiliary current.Optional modules and remote indicators mount in boxes with snap-trak or are gangable behind "Decora" switch plates.NOTE: The FSDACT cannot be used with a one zone fire alarm panel. If the application requires the FSDACT Dialer, you must purchase a panel with three or more zones.
- Battery Cabinet:Gray battery box - holds two batteries
- Battery Cabinet:Red battery box - holds two batteries
- City Tie Module:Reporting events to local energy Master fire alarm box
- End-of-line Resistor:One 3.6K resistor and one 1.1K resistor
- Trim Plate:1, 2, 3 or 4 gang trim plate (white, red or gray) for Remote Annunciator
- DACT/Dialer:Reporting events to a remote monitoring facility
- Configuration Software:PC downloading of configuration and event history
- Relay Module:Five Form C relays (1A each) - configurable as zone or common system mode
- 11 in. Mounting track:Mounting track for 2-4 FSRRMs. Mounts in MFC-A or other listed FA enclosure
- Remote System Indicator:Remote Annunciator Module - common LEDs & sounder w/silence
- Remote Zone Indicator:Remote Annunciator Module - 5 Zone LEDs
- 3 & 5 Zone Trim Ring:Semi-flush mounting of 3 & 5 zone panels (gray or red)
- 10 Zone Trim Ring:Semi-flush moutning of 10 zone panels (gray or red)
- FSRRM Mounting Cabinet :Holds up to 4 FSRRM Modules when used with optional FSRRM-11 snap-track
- Reverse Polarity Module:Reporting alarm status to remote monitoring facility
- Power Supply Expander:Expands 10 zone panel with 2.5 amps additional power
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Features
- 1, 3, 5 or 10 Class B initiating device circuits (IDC)
- 1, 2 or 4 Class B Notification Appliance Circuits
- IDC or NAC pairs convertable to single Class A circuits (10 and 5 IDC panels only)
- Supports 2400, ED2M and SC series detectors
- Zone programmable NACs selectable for Genesis, continuous or temporal output
- Genesis option provides strobe sync and audible silence over two wires
- NAC capacity 1 zone: 1.0 amps
- NAC capacity 3 zone: 1.5 amps
- NAC capacity 5 zone: 2.5 amps
- NAC capacity 10 zone: 2.5 amps expandable to 5.5 amps NAC circuit; 1/2 amp aux current
- Relays for alarm, supervisory and trouble conditions
|
|
 |
 |
 |
 |
|
 |

|