ACC-25/50ZS: 25 watt, 25 VRMS, emergency Voice Evacuation Control Panel (VECP) with integral commercial microphone, digital message generator, zone splitter module (ACCZSM), zone page module with keypad (ACC-ZPMK). The Audio Command Center-25/50 Zoned System (ACC-25/50ZS) is a state-of-the-art Emergency Voice Evacuation
Panel (EVAC) capable of splitting 25 or 50 watts of audio power into up to eight speaker circuits (i.e., zones). The ACC-25/50ZS provides the ability to record five field-programmable messages (up to 60 seconds total message duration) with an integral commercial-grade emergency communications microphone or from an external audio source. Significant technological enhancements set the ACC-25/50ZS apart from other EVAC panels these include full supervision in both active alarm and standby conditions, supervision of amplifier outputs, field wiring, message generator, all tone generators, and the microphone. The integral power supply is capable of charging up to 18 AH batteries, which can be housed in the ACC-25/50ZS cabinet.
The ACC-25/50ZS is suitable for use as an adjunct (slave or stand-alone) to most UL-Listed Fire Alarm Control Panels (FACPs). An optional 25 watt, 25 VRMS audio amplifier is available for system expansion to 50 watts or as a secondary amplifier in jurisdictions requiring such backup. A 70.7 VRMS converter is also available for independently converting amplifiers to meet retrofit needs.
The Zone Splitter Module (ACC-ZSM) divides the output of the Audio Amplifier Module(s) (ACC-AAM25) into up to eight speaker circuits (i.e., zones). The Zone Page Module with Keypad (ACC-ZPMK) provides full manual control of the speaker circuits, status indication of each of the speaker circuits, and automatic control by the FACP via the ACS serial link connection on the MS-9200UD and MS-9600 Addressable Panels. A host of field-programming options, including the capability of five custom messages (fire, tornado, evacuation, hazmat, nonfire, multi-language, etc.) make the ACC-25/50ZS the most versatile voice evacuation system available.
Some Suitable Applications:
- Schools
- Auditoriums
- Dormitories
- Theatres
- Restaurants
- Places of Worship
- Lodging
- Office Buildings
- Factories
STANDARD FEATURES
25 watts of audio power can be divided into eight Style Y (Class B) or four Style Z (Class A) speaker circuits (zones), utilizing the zone splitter module (ACC-ZSM).
Full manual control of all audio zones provided by zone page module with keypad (ACC-ZPMK).
Activation by the FACP using the ACS serial link and/or the five Command (CMD) inputs.
ACS serial link compatible with all FireLite FACPs, depending on function.
FACP automatically directs the voice message to each or all audio zones.
Paging by zone or All-Call.
Full status indication (normal, active, fault) of each speaker circuit.
Fault indication via ACS serial link and/or the two Form-C trouble relays (System and AC Power Loss).
Integral 25 watt, 25 VRMS audio amplifier with single Style Z (Class A) or Style Y (Class B) speaker circuit (expandable to 50 watts using the ACC-AAM25).
Modular design for maximum system flexibility and ease of service.
Two command input circuits can be independently field-programmed for activation by a Notification Appliance Circuit (NAC) or contact closure.
Three command input circuits activate on contact closure.