GENThe FireLite MS-4 and MS-4E Fire Alarm Control Panels
bring the latest in microprocessor technology to conventional fire controls. The MS-4 is compatible with the i³ smoke detectors from System Sensor, and provide such advanced features as drift compensation, maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices is provided, using three selections for manufacturer protocol. The NAC protocol includes the ability to silence audible devices while strobes continue to flash, using only a single pair of wires.
The MS-4 also is compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. For 240 VAC operation, order MS-4E. See the FireLite Device Compatibility Document 15384 for a complete list of compatible devices. NOTE: Unless indicated otherwise, the term MS-4 refers to both MS-4 and MS-4E models.
FEATURES
Four Style B (Class B) IDCs (Initiating Device Circuits).
Two Style Y (Class B) NACs (Notification Appliance Circuits).
Optional module that converts all four IDCs and two NACs
to Class A.
24 VDC.
i³ Technology features:
Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust accumulation.
Maintenance Alert LEDs (per zone) warn of excessive dirt accumulation, preventing false alarms (meets NFPA 72 requirements).
Detector sensitivity is automatically measured by the detector, which automatically adjusts its sensitivity back to the factory settings when it becomes more sensitive due to contaminants settling in the chamber.
Wireless hand-held sensitivity meter eliminates the need for voltmeters, magnets and a physical connection to the detector. The reader displays sensitivity in terms of percent per foot obscuration and provides text status indication.
Supervisory LED (per zone) provides warning if a detector senses temperature approaching freezing.
Special test protocol and LED indication allows quick test of all detectors without need for a ladder.
NAC synchronization features:
Provides synchronization of standard ANSI audible signals as required by NFPA 72.
Provides synchronization of ADA compliant strobes per NFPA 72.
Selectable for System Sensor, Wheelock and Gentex protocols.
Selective Silence feature allows manual silence of horns while strobes continue to flash on the same NAC.
Silent or Audible Walk Test operation mode commanded from the front keypad, with automatic return to normal after one hour of inactivity.
Programmable for combination tamper supervisory monitor and waterflow alarm on one zone.
Alarm verification selectable per zone.
Each zone may be programmed for supervisory or fire, with separate red and yellow LEDs.
Disable switches provided per zone.
NACs programmable for:
Silence Inhibit
Auto Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady signal
Silenceable or Nonsilenceable
Form-C Alarm, Trouble and Supervisory relays.
3.0 A total usable current.
6.0 A total usable current available with optional second transformer.
Optional dress panel (P/N DP-MS2/4).