Home > Shop Brands > FireLite Alarms by Honeywell >

  FireLite ACCZPM Zone Page Module Without Keypad

FireLite ACCZPM Zone Page Module Without Keypad


 

Our Price : $393.95


Product Code: ACCZPM

Qty:

Description
 
The ACC-ZPM Zone Page Module provides annunciation and control for speaker circuits connected to the ACC-ZSM Zone Splitter Module.
Features
  • Make certain that AC and DC power have been removed from the panel.
  • If this module is a replacement for an existing ACC-ZPM, unplug the ribbon cable from connector P2 located on the top edge of the old ACC-ZPM moduleRemove two mounting screws which hold the ACC-ZPM to the mounting bracket standoffs and set aside.
  • Lift the ACC-ZPM from the slot in the bottom of the mounting bracket.
  • Insert the bottom of the new ACC-ZPM in the slot located in the bottom left of the mounting bracket.
  • Secure the module to the mounting bracket standoffs with the two supplied mounting screws.
  • Plug the ribbon cable into connector P2 located on the top edge of the ACC-ZPM. Make certain the other end is connected to P11 located on the bottom left edged of the main circuit board. Note that the ribbon cable
  • connector is keyed to prevent incorrect installation.
  • Program the module S1 DIP switches and S2 & S3 addressing switches as described in the manual Document #51889.
  • Reapply AC and DC power and test the panel for proper operation.