Home > Shop Brands > Keyscan > Peripherals >

 

Keyscan IOCB1616B - IO BOARD ONLY



Keyscan IOCB1616B - IO BOARD ONLY


 

Our Price : $172.20

UPC Code: 800168053302

Product Code: 540349

Qty:

Description
 

• Has 16 inputs and 16 outputs which can be used for custom applications to connect additional devices

within the access control system

• Inputs can monitor contacts on readerless doors, motion sensors, push buttons, or other

sensing devices

• Outputs can activate CCTV cameras, burglar alarm systems, lights, HVAC, parking lot gates,

or other devices

• Single or multiple inputs can be assigned to trip single or multiple outputs – either open

collector or optional form "C" relays – using any of the 7 different modes that include timers,

delays, or pulsing

• Time zones can be assigned to activate and de-activate inputs or outputs

• Includes an enclosure with ample room to mount various IOCB1616

board configurations for flexible installation and wiring

• The access control unit communicates to the IOCB1616 boards

via RS485 over twisted pair cable


FEATURES AND BENEFITS

 

• IOCB1616 module has 16 inputs and 16 outputs

• Connect up to 4 IOCB1616 modules per access control unit for a total of 64 assignable inputs and 64 assignable outputs

• Input/output assignments are programmed via dedicated interface screens on System V Client software

• Permits "and" & "or" logic statements

• Selectable input settings – non supervised or digital, single end of line supervision, or double end of line supervision

• Add up to 2 optional OCB-8 relay boards for form "C" contact outputs

• IOCB1616 includes (1) standard Keyscan enclosure, (1) IOCB1616 circuit board, and (1) DPS-12 power supply

• Enclosure can accommodate up to two IOCB1616 circuit boards with up to 4 optional OCB-8 relay boards

• Compatible with CA4000 or CA8000 controllers only

• Additional modules (IOCB1616B – board only) are available

 

SPECIFICATIONS

 

Power

Dimensions

IOCB1616 -12 VDC, 100 mA board only,

Enclosure -20 1/4" (51.4 cm) H x 16 3/8"

300 mA lock power limit

(41.6 cm) W x 5 5/8" (14.3 cm) D

DPS12 (AUX) -12VDC Output, 1.2A

IOCB1616 – 10 5/8" (26.9 cm) x 3 9/16" (9.1.cm)

Cable Maximums

Environment

Maximum distance from ACU to last IOCB1616 is 2000 feet

Suitable for commercial and industrial applications

2-wire twisted pair

Relative Humidity: 0% to 90% R.H., non-condensing

 

Operating Temperatures: -20o to 71o C (-4o to 160o F)

 

Storage Temperatures: -20o to 85o C (-4o to 185o F)

 

 

 

 

 

 