Description
 
PFC3005 Five Zone Fire Alarm Control Panel

PFC-3005 FIVE ZONE FIRE ALARM CONTROL PANEL

Features
• Five Class ‘B’ initiating circuits
• Two Class ‘B’ indicating circuit
• Individual Zone Silence/Disconnect switches
• Powerful 3mA capacity per zone for 2-wire smoke detectors
• Common alarm Relay contact, Form C, 28 VDC @ 3 AMP (Resistive)
• Selectable ‘N.O’or ’N.C’ common trouble contact 28 VDC @ 3 Amp (Resistive)
• A.C. ON LED (Green)
• Zone Alarm LED (Red)
• Signal Trouble LED (Amber)
• Remote Lamp Fail LED (Amber)
• Ground Fault LED (Amber)
• Battery Fault LED (Amber)
• Alarm Silenced LED (Amber)
• Common Trouble LED & Silence switch
• Remote Trouble Indicator output
• Remote A.C. On output
• Selectable 1 minute Signal silence inhibit
• Extensive Transient Protection on all circuits
• Red exterior color
• Annunciator Outputs available
• All circuits are power limited

The PFC-3005 includes one circuit board providing all the essentials for a complete fire alarm system. Five Class ‘B’ initiating circuits and two Class B indicating circuits are provided by the PFC-3005. The indicating circuit is protected from shorts by self-restoring circuitry.

Supervision includes ground fault detection, battery low level or open wire fault, initiating and indicating circuit wiring faults and loss of A.C. power. Initiating circuits are supervised for opens and ground faults. Indicating circuits are supervised for opens, shorts and ground faults. LED indicators are provided for Zone Alarm, Zone Trouble, A.C. On, Battery Fault, Ground Fault, Common Trouble, Signal Trouble and Signal Silenced. Switches are provided for Zone disconnect/silence, trouble silence and reset. Upon a trouble condition, the trouble LED will flash and the trouble audible signal will pulse. Activating the “Trouble Silence” switch silences the trouble signal and the “Trouble” LED remains flashing.

When the trouble condition clears, the common trouble LED restores to normal and the common trouble buzzer resounds steady until the Trouble Signal silence switch is returned to normal. The alarm signals cannot be silenced for one minute if the one minute inhibit feature has been selected jumper selectable.

The common alarm relay can follow the signal circuit or lock on until the Alarm has been reset. This option is jumper selectable.

Annunciation outputs are provided for alarm, remote trouble indicator and buzzer. Lamp supervision is jumper selectable. The PFC-3005 controls are behind a durable locked door. The cabinet will accommodate a 4 or 6AH battery pack.

3992005 PFC-3005 Five Zone Fire Alarm Panel


Share your knowledge of this product with other customers... Be the first to write a review

Browse for more products in the same category as this item:

Shop Brands > Potter > Fire Systems > Voice Evacuation
Shop Brands > Potter > Fire Systems
Burglar Alarms / Intrusion >

Control Panels for Burglar Alarm Systems

>

Wired Control Panels for Burglar Alarm Systems

> Potter
Fire Alarms > Fire Alarm Control Panels
 
 

Enter your email for a chance to WIN $100 Amex Gift Card.

Please Enter Your Email Address

*One entry per household please