Home >

 

Silent Knight SKE-380-M1-DMR/386-4ZS Pre-Engineered Voice Evacuation System - 40 Watts 25 / 70 VRMS w/ 40-watt amp, digital message repeater, 4 zone splitter w/ Enclosure & Power Supply



Silent Knight SKE-380-M1-DMR/386-4ZS Pre-Engineered Voice Evacuation System - 40 Watts 25 / 70 VRMS w/ 40-watt amp, digital message repeater, 4 zone splitter w/ Enclosure & Power Supply


 

Our Price : $2,633.17


Product Code: 503694

Call for availability

Description
 

SKE-380-M1-DMR/386-4ZS Pre-engineered voice evacuation system with microphone, 40-watt amplifier, digital message repeater, and supervised 4 zone splitter module. 25 or 70 VRMS. (with enclosure and power supply order AU-380-DMPZ.)

Current Requirements: SKE-380


3.0 amps max., in alarm condition*
2000mA in normal standby
20mA in battery saver standby

*Note: If current requirements exceed host panel auxiliary power capacity, an additional separate power supply such as SK Model 5495 or 5499 can be used.

Occupancies defined in NFPA 101, the Life Safety Code, as "areas of assembly," such as restaurants, churches, school gymnasiums, auditoriums and movie theaters may now be required to provide voice evacuation systems when as few as 50 people are present, depending on state and local codes. Silent Knight voice evacuation systems provide tones and voice instructions for organized evacuation of such areas of assembly. Additionally, many of the systems can be used for hazard warning and multi-purpose paging systems when not in use for emergencies.

Features

  • UL Listed, complies with NFPA 72 & 101.
  • Simple 6-wire connection to Silent Knight Fire Controls and other systems.
  • 20 and 40-watt models.
  • Up to 40 half-watt speakers per 20watt module.
  • Up to 80 half-waft speakers per 40watt module.
  • Optional 6 amp power supply (Silent Knight Model 5395).
  • Speaker circuits fully supervised. Short circuit and overload protected.
  • Speaker circuits are power limited.
  • Battery backup from fire alarm control.
  • Battery saver circuit reduces current draw during AC failure conditions.
  • Penetrating slow-whoop alarm signal.
  • Crystal-clear, high-intelligibility voice override.
  • Microphone can be used with or without alarm condition.
  • Digital message repeater uses voice band filtering to assure announcements will be heard even in high noise areas.
  • Low-voltage speaker line. Run up to 3,000 feet with #1 8 guage wire.
  • Updates fire alarm systems to comply with latest safety codes.
  • Designed for new, or retrofit installations using existing wiring and enclosures.
  • All systems pre-engineered at factory. Downloads: SKE-300 Series Spec Sheet (87K PDF file)