This range of light weight all GRP, explosionprrof horns is intended for use in potentially explosive atmospheres and has been designed with high ingress protection to cope with the harsh environmental conditions found offshore and onshore in the oil, gas and petrochemical industries. The flamepaths, flare and the body, are manufactured completely from a UV stable glass reinforced polyester. Stainless steel screws and sinter are incorporated thus ensuring a corrosion free product. A tapered flamepath is used to overcome the problems of assembly of parallel spigot flamepaths. An optional Exe terminal chamber is available.
Specifications:
Certification: UL Listed for USA and Canada:
Hazardous locations:
Class I, Div 2, Groups A, B, C & D Class II, Div 2, Groups F & G. Class I Zones 1 & 2, AExd IIC T4. UL Listing No: E203310.
Ordinary locations: Audible-Signal Device. California State Fire Marshal (CSFM) Listed ATEX Approved: CENELEC EN50014, 18, 19 Cert. No. BAS00ATEX2097X, EExd IIC. Cert. No. BAS00ATEX2098X, EExde IIC. Zones 1 and 2
Material: Body & horn in anti-static, UV stable, glass reinforced polyester, Swivel bracket & captive cover screws in stainless steel Finish: Red Sound Output: DB3 105 ± 3dB(A) at 10 feet (tone dependent)
Weight: 13.2lb./6.0kg approx. Certified Temperature: -67°F to +158°F (-55°C to +70°C) Ingress Protection: NEMA 4x & 6, IP66 and IP67 Voltage: Up to 48V d.c. Up to 254V a.c.
Current Consumption:
12VDC: 760mA 24VDC: 380mA 48VDC: 190mA 110VAC: 135mA 120VAC: 124mA 220VAC: 68mA 230VAC: 65mA 240VAC: 62mA 254VAC: 59m
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Features
- UL Listed for USA and Canada
- Hazardous locations:
- Class I, Div 2, Groups A, B, C & D
- Class II, Div 2, Groups F & G
- Class I, Zones 1 & 2, AExd IIC T4
- Ordinary locations: Audible-Signal Device
- California State Fire Marshal (CSFM) Listed
- ATEX approved
- NEMA 4x &6, IP66 and IP67
- Certified temperature
- All GRP corrosion free flamepaths
- Up to 108dBA output at 10 feet
- Integral volume control
- 27 tones, user selectable
- Two tones may be switched via the external voltage supply
- Horn/Strobe Combination Unit available
|
|
 |
 |
 |
 |
|
 |

|