The MEDC heat detector has been designed for use in hazardous environments. These units are suitable for fire alarm and/or suppression systems in offshore and onshore applications including paint spray booths, flammable material stores, turbine rooms, extract ductwork and other hazardous areas throughout the oil & gas, petrochemical and process industries.
Comprising a Fenwal rate-compensated detector with all-stainless steel external construction, mounted to either a type SM87 marine grade alloy enclosure (Exd version) or JB10 corrosion-free GRP enclosure (Exia, Exem/UL versions). The contact in the detector CLOSES at alarm temperature.
To select appropriate temperature setting, see specification on reverse.
Applications: Compressor turbine/generator skids Switchgear or motor control status rooms Process tank areas or transmission lines
Typical Industries: Power generation Nuclear plants Chemical processing Upstream/downstream oil and gas
Certification: cULus, ATEX, GOST-R, GOST-K, GB Flameproof: ATEX Ex II 2G, Exd IIB T6 Increased Safety: ATEX Ex II 2G, Exem II T6 Intrinsically Safe: ATEX Ex II 1G, Exia IIC T6
Certified Ambient Temperature -20°C to +125°C Exd (T3) ATEX/GOST 'R' -20°C to +55°C Exd (T6)/Exem -55°C to +55°C Exia
Ingress Protection: IP66 & 67 Material: Marine Grade Alloy (Exd) Corrosion-free GRP (Exia/Exem) Temperature Settings: 140°F to 725°F (60°C to 385°C) Entries: 2 × M20 Weight: 1.1-2.0kg (model dependent) Options: Enclosures, color, tag and duty labels, temperature setting
Certifications and Compliances:
Zone 0, Zone 1 and Zone 2 Exia IIC T4/T6, Exd IIB T3/T6 or Exem II T6 ATEX approved -Ex II 1G (Exia) -Ex II 2G (Exd/Exem) BASEEFA certified UL listed for USA and Canada -Class I, Div. 2, Groups A, B, C, D GOST 'R' & 'K' certified Chinese (CQST) certified IP66 & IP67 Certified temperature: -20°C to +125°C (Exd)* -20°C to +55°C (Exem/UL) -55°C to +55°C (Exia) Stainless steel probe Detector temperature settings: 60°C to 385°C, (140°F to 725°F) Marine grade Alloy or GRP enclosure Optional guard
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Features
- Designed for use in hazardous environments
- Suitable for fire alarm and/or suppression systems in offshore and onshore applications including paint spray booths, flammable material stores, turbine rooms, extract ductwork and other hazardous areas throughout the oil and gas, petrochemical and process industries
- Comprising a Fenwal rate-compensated detector with all-stainless steel external construction, mounted to either a type SM87 marine grade alloy enclosure (Exd version) or JB10 corrosion-free GRP enclosure (Exia, Exem/UL versions)
- The contact in the detector CLOSES at alarm temperature
|
|
 |
 |
 |
 |
|
 |

|