[PN# 1043]

Electronic water detection at its best!


The model WB-200 operates on 12 or 24 Volt AC/DC and has a form C relay output that can be connected to alarm panels, bells, dialers, etc. The unit can monitor up to as many as six sensor probes, up to 100 feet away. Each sensor probe has two contacts. When a film of water forms a bridge between these contacts, the unit senses this and triggers the alarm output. The sensor will not alarm due to condensation or high humidity. One standard surface sensor is included with the unit.

 

Typical Applications:

  • Residential or Vacation Homes
  • Basement Sump Pumps
  • Commercial Buildings
  • Office and Computer Areas
  • Unattended Buildings
  • Greenhouses & Animal Buildings
  • All Drain Areas
  • Sprinkler Systems
Features:
  • Versatile 12 or 24 Volt AC/DC power for operation
  • No false alarms due to condensation or humidity
  • Can monitor up to 6 sensor probes - up to 100 feet away
  • Provides (1) form "C" contact closure output for alarm
  • Easy surface mount installation
  • One year parts and labor; subject to conditions of limited warranty.
Specifications:
  • Console Size: 5" x 2.44" x 1.25" (12.7 cm x 6.2 cm x 3.18 cm)
  • Probe Size (standard P/N #1040): 2" x 3" x 0.88" (5.1 cm x 7.6 cm x 2.2 cm)
  • Probe Size (under carpet P/N #1041): 2" x 3" x 0.18" (5.1 cm x 7.6 cm x
    0.5 cm)
  • Power Requirements (resting state): 12V or 24V AC or DC
  • Power Requirements (alarm condition): 5mA @ 12V or 24V AC, or 13.5mA @ 12V or 24V DC
  • Sensitivity: Will not alarm due to high humidity or condensation
  • Operating Temperature: Control and Probe 32? to +140? F (0? to +60? C)
  • Outputs: Form C (SPDT) 1 Amp @ 24Vac, 1 Amp @ 30 VDC (not for direct high voltage switching)
  • Recomended Dist. Between Probes & Console: 1-2 probes: 200ft (61 m) max. 3 or more probes: 100ft (30.5 m) per probe
  • Recommended Max. Probes Per Console: 6

Share your knowledge of this product with other customers... Be the first to write a review

Browse for more products in the same category as this item:

Shop Brands > Winland Electronics > WaterBug Alerts
Shop Brands > Winland Electronics
 
 

Enter your email for a chance to WIN $100 Amex Gift Card.

Please Enter Your Email Address

*One entry per household please