You are here: Home > Shop Brands > FireLite Alarms by Honeywell > Addressable Fire Alarm Control Panels
We found 3 results matching your criteria.
Sort By:
Page of 1
Fire-Lite MS-2E Two Zone Control Panel Fire-Lite MS-9200UDLSC
240 VAC, 50 Hz, 1.15 A operation

The Fire-Lite MS-2 and MS-2E Fire Alarm Control Panels bring the latest in microprocessor technology to conventional fire controls. The MS-2 is compatible with the new i³ smoke detectors from System Sensor, and provides such advanced features as drift compensation, maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices is provided, using three selections for manufacturer protocol. The NAC protocol includes the ability to silence audible devices while strobes continue to flash, using only a single pair of wires. The MS-2 also is compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally- open contact devices. For 240 VAC operation, order MS-2E. See the Fire•Lite Device Compatibility Document 15384 for a complete list of compatible devices. NOTE: Unless indicated otherwise, the term “MS-2” refers to both MS-2 and MS-2E models.

FEATURES
• Two Style B (Class B) IDCs (Initiating Device Circuits).
• One Style Y (Class B) NAC (Notification Appliance Circuit).
• 24 VDC.
• i³ Technology features:
— Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust accumulation.
— Maintenance Alert LEDs (per zone) warn of excessive dirt accumulation, preventing false alarms (meets NFPA 72 requirements).
— Detector sensitivity is automatically measured by the detector, which automatically adjusts its sensitivity back to the factory settings when it becomes more sensitive due to contaminants settling in the chamber.
— Wireless handheld sensitivity meter eliminates the need for voltmeters, magnets and a physical connection to the detector. The reader displays sensitivity in terms of percent per foot obscuration and provides text status indication.
— Supervisory LED (per zone) provides warning if a detector senses temperature approaching freezing.
— Special test protocol and LED indication allows quick test of all detectors without need for a ladder.
• NAC synchronization features:
— Provides synchronization of standard ANSI audible signals as required by NFPA 72.
— Provides synchronization of ADA compliant strobes per NFPA 72.
— Selectable for System Sensor, Wheelock and Gentex protocols.
— Selective Silence feature allows manual silence of horns while strobes continue to flash on the same NAC.
• Silent or Audible Walk Test operation mode commanded from the front keypad, with automatic return to normal after one hour of inactivity.
• Alarm verification selectable per zone.
• Each zone may be programmed for supervisory or fire, with separate red and yellow LEDs.
• Disable switches provided per zone.
• NACs programmable for:
— Silence Inhibit
— Auto Silence
— Strobe Synchronization
— Selective Silence (horn-strobe mute)
— Temporal or Steady signal
— Silenceable or Nonsilenceable
• Form-C Alarm and Trouble relays.
• 3.0 amps total usable current.
• Optional dress panel (P/N DP-MS2/4).

REPLACES FL-MS4424

Built upon the features found in the highly successful MS-9200UD, the new LS model features Fire-Lite's new fast Litespeed polling protocol. Not only does it poll 10 devices at a time, it permits the use of standard unshielded fire wire. The MS-9200UDLS is ideal for commercial, industrial, manufacturing, office buildings, schools, strip malls and other facilities requiring performance-based, sophisticated technology at reasonable cost.
FireLite MS-25E Addressable FACP With Built-in Communicator by Honeywell - 220/240 VAC
The FireLite MS-25(E) is a Fire Alarm Control Panel (FACP) and Digital Alarm Communicator/Transmitter (DACT) combined into one circuit board.

With an extensive list of powerful features, the MS-25 fits into applications previously served only by conventional panels.

This compact, intelligent addressable control panel supports up to 25 Honeywell Fire Systems addressable devices of any type of detectors and modules. With code wheel addressable detectors/modules and JumpStart feature the MS-25 can be Life Safety operational without a single programming tool.

Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Fire-Lite. The MS-25's integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The power supply and all electronics are contained on a single circuit board and housed in a metal cabinet.

Custom programming can be performed through FACP built-in browser (no programming software required) with a PC.

NOTE: Unless otherwise specified, the term MS-25 is used in this data sheet to refer to the MS-25 and the MS-25E. For details on the Canadian version, see DN-60641.

   
 
 
 

Enter your email for a chance to WIN $100 Amex Gift Card.

Please Enter Your Email Address

*One entry per household please