Altronix  AL1012ULXPD16CB - 10 AMP 12 VOLT POWER SUPPLY UL LISTED W/16 PTC. UL LISTED W/16PTC Altronix 600UXP8F - AL600ULXPD8 OLD VERSION WITH TRANSFORMER. 10/11/06 REPLACES AX-600XP8CF

AL1012ULXPD16CB

Power Supply/Charger

Overview

Model AL1012ULXPD16CB power supply converts a 115VAC 60Hz input, to 8 amp of continuous supply current, 10 amp during alarm @ 12VDC distributed via sixteen (16) PTC protected Class 2 Rated outputs. Model AL1012ULXPD16 is a fuse protected version of this unit.

Agency Listings


• UL Listed for Access Control Systems (UL294), CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment File # S4707.
• NFPA 72 Compliant.

Features/Specifications


• 12VDC output.
• 10 amp of continuous supply current.
• Class 2 Rated power limited outputs.
• Sixteen (16) PTC protected outputs.
• 115VAC 60Hz, 1.9 amp input.
• PTCs are rated @ 2.5 amp
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12 ”W x 4.5”D
• 1/2 and 3/4 combination knockouts.

Altronix 600UXP8F - AL600ULXPD8 OLD VERSION WITH TRANSFORMER. 10/11/06 REPLACES AX-600XP8CF

Altronix AL1002TVA - AL1002ULADA WITH DELAYED CHIP Altronix AL1002ULADA - NAC Power Extender. 24VDC @ 10A. Class 2.

AL1002ULADA

NAC Power Extender

Overview

Model AL1002ULADA is an extremely cost effective 10 amp voltage regulated remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers regulated and filtered 24 volt power to Class B or Class A NAC loop circuits. Additionally, a separate 1.0A auxiliary output with reset for four (4)-wire smoke detectors is available. The 10 amp rated supply current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs. The unit also features “Loop Output” trouble memory indication to help identify troublesome sporatic problems. Model is available in a larger enclosure AL1002ULADAJ.

Agency Listings


• UL Listed Control Units and Accessories for Fire Alarm Systems (UL864), Power Supplies for Fire Protective Signaling Systems (UL1481). File# S5075.
• CSFM - California State Fire Marshal Approved. File# 7315-1335:110.
• MEA - NYC Department of Buildings Approved.
• FM Approved.

Features/Specifications

Power Supply/Charger:
• 24VDC output.
• 10 amp max total alarm current.
• 115VAC 60Hz., 4.4 amp.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Logic Board:


• Class 2 Rated power limited outputs.
• Two (2) Class A or two (2) Class B FACP inputs.
• Two (2) NC dry contact trigger inputs.
• Two (2) Class A or four (4) Class B Indicating Circuits.
• Two (2) Class B outputs may be paralleled for more power on an indicating circuit.
• One (1) Aux. Power Output @ 1 amp supply current (w/Battery Back Up).
• Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occured on one or more signaling circuit outputs.
• 2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
• Horn/Strobe sync protocols include: Gentex, System Sensor, Faraday, Amseco.
• Temporal Code 3 Mode.
• Steady Mode.
• Input to Output Follower Mode (maintains synchronization of notification appliance circuits).
• March Time.
• Compatible with 24VDC or 12VDC fire panels.
• Common Trouble inputs and outputs.
• Ground fault detection.
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.

AL1002ULADA

NAC Power Extender

Overview

Model AL1002ULADA is an extremely cost effective 10 amp voltage regulated remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers regulated and filtered 24 volt power to Class B or Class A NAC loop circuits. Additionally, a separate 1.0A auxiliary output with reset for four (4)-wire smoke detectors is available. The 10 amp rated supply current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs. The unit also features “Loop Output” trouble memory indication to help identify troublesome sporatic problems. Model is available in a larger enclosure AL1002ULADAJ.

Agency Listings


• UL Listed Control Units and Accessories for Fire Alarm Systems (UL864), Power Supplies for Fire Protective Signaling Systems (UL1481). File# S5075.
• CSFM - California State Fire Marshal Approved. File# 7315-1335:110.
• MEA - NYC Department of Buildings Approved.
• FM Approved.

Features/Specifications

Power Supply/Charger:
• 24VDC output.
• 10 amp max total alarm current.
• 115VAC 60Hz., 4.4 amp.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Logic Board:


• Class 2 Rated power limited outputs.
• Two (2) Class A or two (2) Class B FACP inputs.
• Two (2) NC dry contact trigger inputs.
• Two (2) Class A or four (4) Class B Indicating Circuits.
• Two (2) Class B outputs may be paralleled for more power on an indicating circuit.
• One (1) Aux. Power Output @ 1 amp supply current (w/Battery Back Up).
• Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occured on one or more signaling circuit outputs.
• 2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
• Horn/Strobe sync protocols include: Gentex, System Sensor, Faraday, Amseco.
• Temporal Code 3 Mode.
• Steady Mode.
• Input to Output Follower Mode (maintains synchronization of notification appliance circuits).
• March Time.
• Compatible with 24VDC or 12VDC fire panels.
• Common Trouble inputs and outputs.
• Ground fault detection.
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.
Altronix AL1002ULADA220 - 10 AMP 220 VOLT 4 OUTPUT ADA POWER SUPPLY. 4 OUTPUT Altronix AL1002ULADAJ - NAC Power Extender. 24VDC @ 10A. Class 2.. Lrg Encl.

Altronix AL1002ULADA220 - 10 AMP 220 VOLT 4 OUTPUT ADA POWER SUPPLY. 4 OUTPUT

AL1002ULADAJ

NAC Power Extender

Overview

Model AL1002ULADAJ is an extremely cost effective 10 amp voltage regulated remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers regulated and filtered 24 volt power to Class B or Class A NAC loop circuits. Additionally, a separate 1.0A auxiliary output with reset for four (4)-wire smoke detectors is available. The 10 amp rated supply current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs. The unit also features “Loop Output” trouble memory indication to help identify troublesome sporatic problems. Model is available in a smaller enclosure AL1002ULADA.

Agency Listings


• UL Listed Control Units and Accessories for Fire Alarm Systems (UL864), Power Supplies for Fire Protective Signaling Systems (UL1481). File# S5075.
• CSFM - California State Fire Marshal Approved. File# 7315-1335:110.
• MEA - NYC Department of Buildings Approved.
• FM Approved.

Features/Specifications

Power Supply/Charger:
• 24VDC output.
• 10 amp max total alarm current.
• 115VAC 60Hz., 4.4 amp.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Logic Board:


• Class 2 Rated power limited outputs.
• Two (2) Class A or two (2) Class B FACP inputs.
• Two (2) NC dry contact trigger inputs.
• Two (2) Class A or four (4) Class B Indicating Circuits.
• Two (2) Class B outputs may be paralleled for more power on an indicating circuit.
• One (1) Aux. Power Output @ 1 amp supply current (w/Battery Back Up).
• Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occured on one or more signaling circuit outputs.
• 2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
• Horn/Strobe sync protocols include: Gentex, System Sensor, Faraday, Amseco.
• Temporal Code 3 Mode.
• Steady Mode.
• Input to Output Follower Mode (maintains synchronization of notification appliance circuits).
• March Time.
• Compatible with 24VDC or 12VDC fire panels.
• Common Trouble inputs and outputs.
• Ground fault detection.
• Lifetime Warranty.

Enclosure


• Accommodates up to four (4) 12VDC/12AH batteries.
• Dimensions: 18”H x 14.5”W x 4.625”D.
• 1/2" and 3/4" combination knockouts.
Altronix AL1012ULACM - 8 Fused Outputs Power Supply/Access Power Controller. 12VDC @ 10A. Altronix AL1012ULM - 5 PTC Outputs Access Control Power Supply Charger. 12VDC @ 10A. Grey Encl.

AL1012ULACM

Power Supply/Charger w/Multi
-Output Access Power Controller

Overview

Model AL1012ULACM converts a 115VAC 60Hz input into eight (8) independently controlled 12VDC non power limited fuse protected Fail
-Safe and/or Fail
-Secure outputs with a total of 10 amp continuous supply current. The fire alarm disconnect feature enables emergency egress in the event the fire alarm system is activated. It is individually selectable for any or all of the eight (8) outputs. Model AL1012ULACMCB is a PTC protected version of this unit.

Agency Listings


• UL Listed for Access Control Systems (UL294), CUL Listed
- CSA Standard C22.2 No.205
-M1983, Signal Equipment. File# BP6714.

Features/Specifications

Power Supply/Charger:
• 12VDC output.
• 10 amp of continuous supply current.
• 115VAC 60Hz, 1.9 amp input.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built
-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Access Power Controller:


• Eight (8) Access Control System outputs.
- Eight (8) fuse protected Fail
-Safe and/or Fail
-Secure 12VDC or 24VDC power outputs.
- Any power output may be converted to dry form "C" relay output.
- Eight (8) fuse protected 12VDC auxiliary power outputs (unswitched).
• Red LEDs indicate outputs are triggered (relays energized).
• Eight (8) Access Control System trigger inputs.
- Eight (8) normally open (NO) inputs.
- Eight (8) open collector inputs.
- Any combination of the above.
• Fire Alarm Disconnect:
- Fire Alarm Disconnect (latching or non
-latching) is individually selectable for any or all of the eight (8) outputs.
- Normally open (NO) or normally closed (NC) dry contact input.
- Polarity reversal input FACP signaling circuit.
• Fire Alarm trigger LED indicates that the Fire Alarm Disconnect has been activated.
• Fire Alarm output relay for triggering auxiliary reporting devices (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.

AL1012ULM

Multi-Output Access Control Power Supply Charger

Overview

Model AL1012ULM is specifically designed for use with access control systems and accessories. This unit converts a 115VAC 60Hz input into five (5) PTC protected 12VDC @ 10 amp Class 2 Rated power limited outputs.

Agency Listings


• UL Listed for Access Control Systems (UL294), CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment. File# S4707.

Features/Specifications

Power Supply/Charger:
• 12VDC output.
• 8 amp with 10 amp during alarm supply current.
• 115VAC 60Hz, 1.9 amp input.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Multi-Output Module:


• Five (5) PTC protected outputs.
• Class 2 Rated power limited outputs.
• Current limit is 2 amp @ 12VDC per output.
• Provides power for Fail Safe and/or Fail Secure locking devices.
• Fire Alarm Panel or Access Control System trigger inputs. NO or NC supervised trigger input and polarity reversal trigger input (.4 amp draw from FACP).
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.
Altronix AL1012ULX - Single Output Power Supply/Charger. 12VDC @ 10A. Grey Encl. & Xfmr. Altronix AL1012ULXB - Off-line Switching Power Supply Board. 12VDC @ 10A.

AL1012ULX

Power Supply/Charger

Overview

Model AL1012ULX power supply converts a 115VAC 60Hz input, to 12VDC @ 10 amp of continuous supply current.

Agency Listings


• UL Listed for Access Control Systems (UL294), CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment. File# BP6714.

Features/Specifications


• 12VDC output.
• 10 amp of continuous supply current.
• 115VAC 60Hz, 1.9 amp input.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Enclosure


• Accommodates up to one (1) 12VDC/12AH battery.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.

AL1012ULXB

Power Supply/Charger

Overview

Model AL1012ULXB power supply converts a 115VAC 60Hz input, to 10 amp of continuous supply current @ 12VDC non-power limited output.

Agency Listings


• UL Recognized Component for Access Control Systems (UL294). File# BP6714.

Features/Specifications


• 12VDC output.
• 10 amp of continuous supply current.
• 115VAC 60Hz, 1.9 amp input.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Board


• Dimensions (approximate): 4.5”W x 7.5”L x 2.25”H.
Altronix AL1012ULXPD16 - 16 Fused Outputs Power Supply/Charger. 12VDC @ 10A. Grey Encl. & Xfmr. Altronix AL1012ULXPD4 - 4 Fused Outputs Power Supply/Charger. 12VDC @ 10A. Grey Encl. & Xfmr.

AL1012ULXPD16

Power Supply/Charger

Overview

Model AL1012ULXPD16 power supply converts a 115VAC 60Hz input, to 8 amp of continuous supply current, 10 amp during alarm @ 12VDC distributed via sixteen (16) fuse protected non power limited outputs. Model AL1012ULXPD16CB is a PTC protected version of this unit.

Agency Listings


• UL Listed for Access Control Systems (UL294), CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment. File# S4707.
• NFPA 72 Compliant.

Features/Specifications


• 12VDC output.
• 10 amp of continuous supply current.
• Sixteen (16) fuse protected outputs.
• Fuses are rated @ 3.5 amp.
• 115VAC 60Hz, 1.9 amp input.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.

AL1012ULXPD4

Power Supply/Charger

Overview

Model AL1012ULXPD4 power supply converts a 115VAC 60Hz input, to 10 amp of continuous supply current @ 12VDC distributed via four (4) fuse protected non power limited outputs. Model AL1012ULXPD4CB is a PTC protected version of this unit.

Agency Listings


• UL Listed for Access Control Systems (UL294), CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment. File# S4707.
• NFPA 72 Compliant.

Features/Specifications


• 12VDC output.
• 10 amp of continuous supply current.
• Four (4) fuse protected outputs.
• Fuses are rated @ 3.5 amp
• 115VAC 60Hz, 1.9 amp input.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type battery backup.
• Maximum charge current .7 amp.
• Zero voltage drop upon transfer to battery backup.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact rated @ 1 amp 28VDC).
• Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Lifetime Warranty.

Enclosure


• Accommodates up to two (2) 12VDC/12AH batteries.
• Dimensions: 15.5”H x 12”W x 4.5”D.
• 1/2" and 3/4" combination knockouts.
   
 
 
 