Overview
The American Power Conversion® Basic Rack
PDU distributes power to devices in the rack.
Outlets. The Rack PDU has twenty IEC-320-C13
outlets, and four IEC-320-C19 outlets.
Power cord. The 10-foot (3.05-meter) power cord
terminates with a IEC-309 32 A connector.
Electrical
Input connector IEC-309 32 A plug
Output connectors 20 – IEC-320-C13,
4 – IEC-320-C19 outlets
Nominal input voltage 230 VAC
Acceptable input voltage ± 10% of normal voltage
Input frequency 49– 63 Hz
Physical
Size (H × W × D) 63.75 × 2.19×1.73 in
(161.92 × 5.56×4.39 cm)
Shipping Dimensions
(H × W × D) 84.00 × 6.00×5.00 in
(213.36 × 15.24×12.7 cm)
Weight 12.25 lb (5.56 kg)
Shipping weight 14.25 lb (6.46 kg)
Environmental
Elevation (above MSL)
Operating
Storage
0 – 15,000 ft (0 – 4500 m)
0 – 50,000 ft (0 – 15 000 m)
Temperature
Operating
Storage
–5 to 45° C (23 to 115° F)
–25 to 65° C (–13 to 149° F)
Humidity
Operating
Storage
5 – 95% RH non-condensing
5 – 95% RH non-condensing
Compliance
Safety verification VDE, CE