Edwards 282B-PL Rate Of Rise and Fixed Temperature Heat Detector; 3 Amp At 6 - 125 Volt AC/1 Amp At 6 - 24 Volt DC/0.3 Amp At 125 Volt DC/0.1 Amp At 250 Volt DC Pure White Surface/Ceiling/Flush Mount

Edwards 282B-PL Rate Of Rise and Fixed Temperature Heat Detector; 3 Amp At 6 - 125 Volt AC/1 Amp At 6 - 24 Volt DC/0.3 Amp At 125 Volt DC/0.1 Amp At 250 Volt DC Pure White Surface/Ceiling/Flush Mount
EDWARDS SIGNALING
ED-282BPL
 
Quantity
In Stock

Usually leaves our warehouse the same business day.

Reviews:

0 [0]
Edwards 280B-PL series heat detectors offer fixed temperature or combination rate-of-rise and fixed temperature detection. A temperature increase at the sensor of 15F (9C) or more per minute activates the rate-of-rise feature, closing the contacts in the sensor to transmit the alarm conditions to the fire alarm control panel. When the rate-of-rise element alone has been activated, the sensor is self-restoring. If the temperature of the center disk rises to the sensor's rated temperature, the fixed temperature element activates, closing contacts in the sensor and transmits an alarm condition to the fire alarm control panel. The fixed temperature element is non-restorable and, when activated, the detector must be replaced. The need for replacement is indicated when the center disk has fallen free from the detector.